PowerQuality Solutions

PowerQuality Solutions

Featured news

Show All

With the new energy saving calculator you can calculate your annual savings of energy costs and CO2.

Read more

POWER QUALITY - MORE THAN JUST THE COMPLIANCE OF EMC Directives

Presently electricity producers and suppliers are responsible for ensuring that the public supply conforms to the power quality standard EN 50160. However, it is in their own interest for electrical plant operators to minimize disruptions to the grid and so reduce production losses caused by system faults.

In addition to problems such as harmonics and voltage dips there is also the more important issue of saving energy to preserve our resources. REO follows a holistic approach, under the title of „Power Quality“, which considers the needs of both the nertwork and the consumers.

Thus, the core activity of REO AG is to find the very best solutions for maintaining the quality of our power supply.

Power Quality Solutions

Products such as Line filters and reactors, dv / dt filters and reactors, sinusoidal filters, regenerative filter and the harmonic filter REOWAVEPassive contribute not only to  prevent  disturbances, but  to save energy, too .

For example, by using a REOWAVE passive filter, up to 30 % energy savings can be achieved.

These are just some of the solutions that we offer in the field of power quality for you. In addition to power reactors, EMC and harmonic filters , we also offer customized solutions and services like EMC measurements - talk to us !

  • CNW 8981-50 Hz

    REOWAVEpassive - harmonic filter 50 Hz/400V (IP20)

    CNW 8981-50 Hz
    • Nominal Voltage: 400 V
    • Rated current: 6 - 1200 A
    • Frequency: 50 Hz

    Reduce Harmonics - save up to 30% energy costs.


    The REOWAVE®passive filters harmonics caused by  the B6 circuit (thyristor, diode bridge, etc.) and motor drives. The supply network is relieved by compensating the harmonics reactive power. This enables cost savings in material selection and energy consumption. Starting currents and current peaks are greatly attenuated.


    This increases the service life and reliability of electrical systems. Due to the compact and ready-build  an easy installation is possible.


    The REOWAVE®passive helps to comply with international power quality standards IEEE 519 or EN 61000-3.



    •  Nominal voltage: 400V

    • Frequency: 50Hz

    • In accordance with: EN 60289 / EN 61558

    • Test voltage: L-L 2500 V, DC 1min; L-PE 2500 V, DC 1min

    • Insulation class: T40 / F

    • Climate class: IEC 60068-1 DIN

    • Protection: IP 20 (also available as IP00 version)

    • Nominal voltage: 400V / 50 Hz

    • Standards: IEEE 519, EN 61000-3-12, EN 61000-3-2, IEC 61000-3-4


     

  • CNW 903

    Three-phase mains choke 4% Uk

    CNW 903
    • Nominal Voltage: 3 x 500 V
    • Rated current: 3-1200 A
    • Inductance: 9,800-0,024 mH

    Power Noise Reduction - save up to 20% energy costs. A mains choker relieved the supply network by compensating the harmonics reactive power. The harmonics and commutation notches are reduced strongly. By using a mains choke the inverter electronics and DC-capacitors will be protected.


    Starting currents and current peaks are reduced up to 60%. Mains chokes helps to comply with international power quality standards IEEE 519 or EN 61000-3-2.



    • Rated voltage: U ≤ 3 x 500 V 

    • Short circuit: Uk 4% (400VAC/50Hz, INenn)

    • Frequency: 50/60 Hz

    • According to: EN 60289 / EN 61558

    • Test voltage: L-L 2500 V, DC 1min; L-PE 2500 V, DC 1min

    • Insulation class: T40/F

    • Protection rating: IP00

    • Climatic categorie: DIN IEC 60068-1

    • Overload: 1,5 x INenn 1 min / h

    • Design: mounted on footprint


     


    Typical applications



    • Drive systems for motor drives:


      • Mechanical engineering

      • Elevators / escalators

      • Pipes

      • Conveyor technology

      • Ventilation and air conditioning

      • Robotics

      • Automation technology


    • Power supplies

    • Wind turbines



  • CNW 933

    Three-phase sinusoidal filter

    CNW 933
    • Nominal Voltage: 500 V
    • Rated current: 2 - 1200 A
    • Inductance per strand: 0,05 - 25 mH

    Sinusoidal output current - save costs and trouble-free operation.


    For particularly long cable lengths of > 100m between inverter and motor the shielded cable for EMI suppression used can cause a capacitive coupling. A conventional motor choke can not provide sufficient damping in such cases.


    The sinusoidal filter is a low pass from inductance and capacitance and has a very low resonance frequency. So it is able to generate a largely sinusoidal current. The operation and the loss balance of the asynchronous motor behave like the normal mains operation. The typical motor noise with converter do not occur and a shielded cable to the motor can be dispensed. Losses and heating are greatly minimized and the leakage current will be reduced. Longer motor cable lengths are possible. The motor insulation is protected, thus increasing the service life.


    The sinusoidal filter also attenuates the conducted interference in lower frequency range very good. The losses and the typical noise in the motor plate can be reduced.



    • Rated voltage: U ≤ 3 x 500 V

    • Max. voltage ripple: 5%

    • Field frequency: 0 - 60 Hz

    • Drive switching frequency: up to 150 A >4kHz, from 150 A >1,5KHz

    • Short-circuit voltage Uk: 8% (bei 400V)

    • Voltage drop: 18,4 V/Strang (bei IN und 50Hz)

    • Max. Cable length to the motor: 600 m (unshielded) 1000m (shielded)

    • According to: EN 60289 / EN 61558

    • Test voltage: L-L 2500 V, AC/50Hz 60s; L-PE 2500 V, AC/50Hz 60s

    • Insulation class: T40/F

    • Protection class: IP00

    • Climatic category: DIN IEC 60068-1

    • Overload: 1,5 x INenn 1 min / h

    • Ambient temperature: 40 °C

    • Design: standing on foot angle



    Typical applications



    • Drive systems for motor drives:


      • Mechanical engineering

      • Elevators / escalators

      • Pipes

      • Conveyor technology

      • Ventilation and air conditioning

      • Robotics

      • Automation technology


    • Power supplies

    • Wind turbines

  • CNW 957

    Regenerative harmonics filter (400V/50 Hz)

    CNW 957
    • Nominal Voltage: 400 V
    • Rated current: 14 - 74 A

    LCL filters are used especially in regenerative converters (AFE), but also for inverters for renewable energies. The main purpose of this filter is to eliminate the PWM frequencies for protect the supply network.



    • Rated voltage: 3 x 400V / 50Hz 

    • Climatic categorie: 25/085/21 DIN IEC 68 Part 1

    • Ambient temperature: 40°C

    • Protection rating: IP00

    • Optional: available with charging resistor



  1. Page:
  2. 1
  3. 2

Downloads

  • Download
    PowerQuality Solutions
    pdf 4.00 KB

    PowerQuality Solutions

    Powerful solutions for trouble-free power
    Download
  • Download
    Energy saving with mains chokes and harmonic filters
    pdf 4.00 KB

    Energy saving with mains chokes and harmonic filters

    Save up to 30% energy!
    Download
  • Download
    Treatise Harmonic absorption filter
    pdf 4.00 KB

    Treatise Harmonic absorption filter

    Treatise Harmonic absorption filter
    Download
  • Download
    Treatise PowerQuality
    pdf 4.00 KB

    Treatise PowerQuality

    Treatise PowerQuality
    Download
  • Download
    REO energy savers
    pdf 4.00 KB

    REO energy savers

    Save money with less reactive power
    Download
  • Download
    HF-components Product catalogue
    pdf 4.00 KB

    HF-components Product catalogue

    Product catalogue
    Download
  • Download
    REOWAVEpassive
    pdf 4.00 KB

    REOWAVEpassive

    The new generation of harmonic filters
    Download
  • Download
    REO Regenerative Line Reactors CNW 953
    pdf 4.00 KB

    REO Regenerative Line Reactors CNW 953

    REO Regenerative Line Reactors CNW 953 for the use with regenerative converters
    Download