CNW 953

Three-phase filter choke 12% Uk

CNW 953

Unique Selling Point


  • Suitable for Regenerative converters
  • Compact design
  • Extended service life of electrical consumers
  • Attenuation of current spikes of up to 60%
  • Reduction of the input current
  • Low noise
  • Production according to UL insulation system E251513 possible

Description


Reduce network disturbances - saving energy costs.

The CNW 953 series has been developed especially for smoothing flows in regenerative converters. The series is designed for normal operation as mains choke and also for the regenerative feedback operation for smoothing of the current.The CNW 953 is also suitable for use as a filter choke in LCL filters.

By using a mains choke the inverter electronics and DC bus capacitors are protected.

Starting currents and current peak are attenuated up to 60%. 

Mains chokes help to comply with international power quality standards IEEE 519 or EN 61000-3-2.

  • Rated voltage: U ≤ 3 x 690 V
  • Short circuit: Uk 12% (690VAC/50Hz, INenn)
  • Frequency:  50/60 Hz
  • According to: EN 60289 / EN 61558
  • Test voltage: L-L 3000 V, 50Hz 60s; L-PE 3000 V, 50Hz 60s
  • Insulation class: T50/F
  • Protection rating: IP00
  • Climatic categorie: DIN IEC 60068-1
  • Overload: 1,5 x INenn 1 min / h
  • Design: standing on foot angle

 

Typical applications

  • Drive systems for motor drives:
    • Mechanical engineering
    • Elevators / escalators
    • Conveyor technology
    • Automation technology
  • Wind turbines
  • Solar systems

Technical Data


  • Nominal Voltage : 690 V
  • Rated current : 200 - 1200 A
  • Inductance : 0,127 - 0,761 mH

Cirucit example

Your contact: +49 - 212 8804-0 • info@reo.de

CNW 953

Three-phase filter choke 12% Uk

Technical data

Type

Rated voltage
U [V]

Rated current
IN [A]

Inductance
L [mH]

Losses
P [W]

Weight
[kg]

CNW 953/200

 3 x 690 V

50/60 Hz

 

 

 

200

0.761

730

131

CNW 953/250

250

0.609

840

160

CNW 953/300

300

0.507

980

184

CNW 953/350

350

0.435

1110

214

CNW 953/400

400

0.380

1480

229

CNW 953/500

500

0.304

1750

271

CNW 953/600

600

0.254

2060

316

CNW 953/700

700

0.217

2450

342

CNW 953/800

800

0.190

2630

387

CNW 953/900

900

0.169

2970

410

CNW 953/1000

1000

0.152

3240

456

CNW 953/1200

1200

0.127

4060

558

Higher power ratings

 

For Europe

For USA

Frequency: 50 Hz

Frequency: 60 Hz

Short circuit voltage Uk: 4% (by 400V)

Short circuit voltage Uk: 9,6% (by 200V)

Voltage drop: 9,23 V/branch

Voltage drop: 11,05 V/branch

Your contact: +49 - 212 8804-0 • info@reo.de

CNW 953

Three-phase filter choke 12% Uk

 

Dimension drawing


 

Dimensions

Type

Length
L [mm]

Width
B [mm]

High
H [mm]

Mounting
N1 [mm]               N2 [mm]

Connection
Lowly Cu

CNW 953/200

480

260

492

356

188

30 x 4

CNW 953/250

480

289

492

356

218

30 x 4

CNW 953/300

540

288

560

450

174

30 x 4

CNW 953/350

540

308

611

450

184

40 x 5

CNW 953/400

540

318

605

450

204

40 x 5

CNW 953/500

600

326

634

500

224

40 x 5

CNW 953/600

600

351

677

500

239

40 x 8

CNW 953/700

660

367

701

550

224

40 x 8

CNW 953/800

660

398

704

550

244

60 x 5

CNW 953/900

660

419

706

550

254

60 x 10

CNW 953/1000

720

415

764

590

239

60 x 10

CNW 953/1200

780

432

791

650

275