Unique Selling Point


  • Fully encapsulated
  • Glass-fibre reinforced cast housing
  • High-precision current measurements Cl 0.2
  • Pulsed current measurement 
    (8/20μs surge current pulse)
  • Low-loss core (core losses
    <10W/kg at 20kHz/200mT) 
  • Housing made of UL-V0 material with inset thread

Description


Because of the materials selected, REO pulsed current transformers in the IN-I series monitor current with high precision and in the appropriate transformation ratio - which makes them particularly suitable for power measurements, current monitoring and analysis, and for use in solar inverters. They are ideal for use in active filters, as they can be designed to measure current surges.

The primary current is measured in a conductor fed through the closed toroidal core.

The magnetic field generated by the flow of current through the conductor is detected by the toroidal core, which, in accordance with the transformation ratio of the secondary winding, generates a smaller current for measurement purposes. By this means, a heavy current to be measured is reduced to a substantially smaller current and is in addition isolated from the primary circuit by safe electrical isolation.

  • According to: EN60044-1
  • Primary rated current: 50 - 200 A
  • Frequency: 50 - 50.000 Hz

Application area

  • Metrology and testing techniques


Technical Data


  • Primary rated current : 50 - 200 A

Mode of operation

Your contact: +49 - 212 8804-0 • info@reo.de

Series IN-I

Pulsed current transformer

Technical data

Type IN-I

 

50

100

200

 

IPN 

Primary rated current

r.m.s

0 - 50

0 - 100

0 - 200

[A]

ImaxPN

Max. primary rated current

r.m.s

± 60

± 120

± 240

[A]

IaN

Rated output current

r.m.s

0 - 50

0 - 100

0 - 200

[mA]

Psek

Rated power

 

0,5

1,0

1,5

[VA]

RB

Load resistance

 

200

100

37,5

[Ω]

URB

Load voltage

r.m.s

10

7,5

[V]

KN

Ratio

1:

1000

 

FU

Measuring accuracy [50 Hz]

 

± 0,2

[%]

f

Frequency

 

0,050 bis 50

[kHz]

TA

Ambient temperature

 

-20 bis +70

[°C]

Vp

Insolation test voltage

r.m.s 50 Hz

3

[kV]

General data

A

Connection

Strands

150

[mm]

TS

Storage temperature

 

-25 bis +85

[°C]

RS

Secondary coil resistance

@ TA = 25 °C

11,5

9

[Ω]

m

Weight

 

0,270

[kg]

 

Standards

 

EN60044-1

 

CTI

Tracking resistance               

Housing / Resin

550 / 600M

 

dCp

Creepage

 

10

[mm]

dCI

Air distance

 

9

[mm]

Your contact: +49 - 212 8804-0 • info@reo.de