Download PDF
Your contact: +49 - 212 8804-0 • info@reo.de

CNW 202

Single-phase mains filters (2 lines, two-stages)

CNW 202

Unique Selling Point


  • easy installation
  • small mounting surface in the cabinet
  • good heat dissipation
  • suitable for use with most frequency converters
  • terminal or cable connection
  • special cable lengths on request
  • very high damping with small leakage current

Description


Applications: Frequency converters for motor drives, wind power installations and power supply units.

  • Conforming to: VDE 0565-3 / IEC 950 / UL 1283
  • Test voltage: L-L 2100 V,DC 1s, L-PE 2700 V,DC 1s
  • Overload: 1,5 x I 1 min/h
  • Climatic category: DIN IEC 68 Teil 1 25/085/21

Technical Data


  • Nominal Voltage : 270 - 480 V
  • Rated current : 7 - 180 A

Recommended filter for suppressing interference according to EN 55011, Class A and EN 61800-3, category C2. By using the REO-Type CNW 201 1-phase-filters, noise levels are reduced to within the European Standard limits specified in EN 50081-2.

The filter creates by using a EMC-compliant and single step design a good damping result. This allows the using of the filter in residential areas with strict requirements.
 -1 Residential area
-2 Industrial area

Circuit example

 

Your contact: +49 - 212 8804-0 • info@reo.de

CNW 202

Single-phase mains filters (2 lines, two-stages)

Technical data

Type

Rated voltage

[V]

Rated current

[A] 

Leakage current

[mA]

L

[mH]

Cx

[µF]

Cy

[nF]

R

[kOhm]

CNW 202/7

270 / 480 V

7

<30

5,4

2,2

200

560

CNW 202/16

16

<30

3,0

2,2

200

560

CNW 202/30

30

<30

2,6

2,5

200

560

CNW 202/42

42

<30

2,6

2,5

200

560

CNW 202/55

55

<30

0,18

4,4

200

560

CNW 202/75

75

<30

0,37

4,4

200

560

CNW 202/100

100

<30

0,26

4,4

200

560

CNW 202/130

130

<35

0,38

4,4

200

560

CNW 202/180

180

<35

0,24

4,4

200

560

Frequency 50/60 Hz

Your contact: +49 - 212 8804-0 • info@reo.de

CNW 202

Single-phase mains filters (2 lines, two-stages)

Dimensions

 

Type

Input

Output (optional)

L1
[mm]

 L2
[mm]
 L3
[mm]
 L4
[mm]
 B1
[mm]
 B2
[mm]
 B3
[mm]
 H 
[mm]

CNW 202/7

Klemme 4 mm2

Litz wire(1,5 mm2)

2

255

240

225

300

50

25

6,5

126

CNW 202/16

Klemme 4 mm2

Litz wire (1,5 mm2)

2

255

240

225

300

50

25

6,5

126

CNW 202/30

Terminal 6 mm2

Litz wire (4 mm2)

3

335

320

305

400

60

35

6,5

150

CNW 202/42

Terminal 10 mm2

Litz wire (10 mm2)

4

330

314

300

500

70

45

6,5

185

CNW 202/55

Terminal 25 mm2

Litz wire (16 mm2)

5

330

314

300

500

80

55

6,5

185

CNW 202/75

Terminal 25 mm2

---

5

330

314

300

---

80

55

6,5

220

CNW 202/100

Terminal 50 mm2

---

6

380

364

350

---

90

65

6,5

220

CNW 202/130

Terminal 50 mm2

---

6

430

414

400

---

110

85

6,5

240

CNW 202/180

Terminal 95 mm2

---

7

430

414

400

---

110

85

8,0

240

Your contact: +49 - 212 8804-0 • info@reo.de

CNW 202

Single-phase mains filters (2 lines, two-stages)

Insertion loss