Download PDF
Your contact: +49 - 212 8804-0 • info@reo.de

CNW 105

Three-phase mains filters (4 lines, single stage)

CNW 105

Unique Selling Point


  • compact construction
  • easy installation
  • low temperature rise
  • good damping performance at 
  • a low leakage current 
  • touch-proof terminals

Description


Applications: Power supply units for data systems engineering, telecommunications, medical equipment and industrial applications

  • Conforming to: VDE 0565-3 / IEC 950 / UL 1283
  • Test voltage: L-L 2100 V, DC 1s, L-PE 2700 V, DC 1s
  • Overload: 1,5 x I 1 min/h
  • Climatic category: DIN IEC 68 Teil 1 25/085/21

Technical Data


  • Nominal Voltage : 480 V
  • Rated current : 3 - 150 A

Recommended filter for suppressing interference according to EN 55011, Class A and EN 61800-3, category C2.

By using a REO three-phase mains filter CNW 105 the noise level is reduced below the prescribed maximum value.

REO mains filters are suitable for individual and collective suppression. For collective suppression: As long as the rated current for each phase remains below the permissible extent, multiple devices can be suppressed.

Circuit example

 

Your contact: +49 - 212 8804-0 • info@reo.de

CNW 105

Three-phase mains filters (4 lines, single stage)

Technical data

Type

Rated voltage

[V]

Rated current

[A]

Leakage current

[mA]

Cx

[µF]

Cy

[nF]

L

[mH]

R

[kOhm]

CNW 105/3

3 x 440

4 x 3

<3,5

0,5

40

4,0

560

CNW 105/6

4 x 6

<3,5

0,5

40

2,4

560

CNW 105/10

4 x 10

<3,5

0,5

40

1,0

560

CNW 105/16

4 x 16

<7

1

43

1,6

560

CNW 105/25

4 x 25

<7

1

43

1,4

560

CNW 105/36

4 x 36

<7

2,2

44

1,2

560

CNW 105/50

4 x 50

<7

2,2

44

0,75

560

CNW 105/80

4 x 80

<14

3,5

110

0,5

560

CNW 105/120

4 x 120

<14

3,5

110

0,25

560

CNW 105/150

4 x 150

<14

3,5

110

0,35

560

Your contact: +49 - 212 8804-0 • info@reo.de

CNW 105

Three-phase mains filters (4 lines, single stage)

Dimensions

Type

Housing

Connection

PE-Connection

B1
[mm]

B2
[mm]

B3
[mm]

D
[mm]

H
[mm]

L1
[mm]

L2
[mm]

L3
[mm]

CNW 105/3

A

6,3 mm Flat plug

6,3 mm Flat plug

53

---

---

5,3

40

110

100

90

CNW 105/6

A

6,3 mm Flat plug

6,3 mm Flat plug

53

---

---

5,3

40

110

100

90

CNW 105/10

A

6,3 mm Flat plug

6,3 mm Flat plug

53

---

---

5,3

40

110

100

90

CNW 105/16

B

Klemme 4mm2 

Earthing bolt (M5)

98

88

70

5,3

70

172

150

90

CNW 105/25

B

Terminals 6mm2 

Earthing bolt (M5)

98

88

70

5,3

70

179

150

90

CNW 105/36

B

Terminals 10mm2 

Earthing bolt (M5)

148

130

120

7,0

70

270

240

160

CNW 105/50

B

Terminals 25mm2 

Earthing bolt (M6)

148

130

120

7,0

70

278

240

160

CNW 105/80

B

Terminals 25mm2 

Earthing bolt (M8)

168

150

140

7,0

110

278

240

160

CNW 105/120

B

Terminals 50mm2 

Earthing bolt (M12)

168

150

140

7,0

110

327

240

160

CNW 105/150

B

Terminals 50mm2 

Earthing bolt (M12)

168

150

140

7,0

110

327

240

160

Your contact: +49 - 212 8804-0 • info@reo.de

CNW 105

Three-phase mains filters (4 lines, single stage)

Insertion loss