Sinusoidal filter

Sinusoidal filter

Sinus filters - Cost savings through use of unshielded cables

Sinusoidal output voltage for  your frequency converter

Advantages of REO Sinus filter :

 - Output voltage is sinusoidal

- Also suitable for very long motor cables

- Shielded motor cable is not required , cost savings up to 1800 , - EUR *

- The efficiency of the overall system is increased

- Reduce motor noise and eddy current losses

 

* Please refer to further information : REO Performance miracle

  • CNW 931

    Single-phase sinusoidal filter 6,15% Uk

    CNW 931
    • Nominal Voltage: 230 V
    • Rated current: 3 - 16 A
    • Inductance per strand: 2,8 - 15 mH

    Smoothing of the current and voltage in order to realize long connecting paths.



    • Ambient temperature: 50 °C

    • Protection rating: IP 00

    • Insulation class: F

    • Linearity: LN bei 1,2 x IN u. ≥ 0,8 x LN bei 1,5 x IN

    • Test voltage: 3 kV

    • Rated voltage: 230 V

    • Uk: 6.15 % 

    • Overload category: 2

    • Pollution degree: 2 

    • Cooling: AN

    • Switching frequency: ≥ 4 kHz 

    • Current ripple: ≤ 20 % bei 4 kHz



  • CNW 933

    Three-phase sinusoidal filter

    CNW 933
    • Nominal Voltage: 500 V
    • Rated current: 2 - 1200 A
    • Inductance per strand: 0,05 - 25 mH

    Sinusoidal output current - save costs and trouble-free operation.


    For particularly long cable lengths of > 100m between inverter and motor the shielded cable for EMI suppression used can cause a capacitive coupling. A conventional motor choke can not provide sufficient damping in such cases.


    The sinusoidal filter is a low pass from inductance and capacitance and has a very low resonance frequency. So it is able to generate a largely sinusoidal current. The operation and the loss balance of the asynchronous motor behave like the normal mains operation. The typical motor noise with converter do not occur and a shielded cable to the motor can be dispensed. Losses and heating are greatly minimized and the leakage current will be reduced. Longer motor cable lengths are possible. The motor insulation is protected, thus increasing the service life.


    The sinusoidal filter also attenuates the conducted interference in lower frequency range very good. The losses and the typical noise in the motor plate can be reduced.



    • Rated voltage: U ≤ 3 x 500 V

    • Max. voltage ripple: 5%

    • Field frequency: 0 - 60 Hz

    • Drive switching frequency: up to 150 A >4kHz, from 150 A >1,5KHz

    • Short-circuit voltage Uk: 8% (bei 400V)

    • Voltage drop: 18,4 V/Strang (bei IN und 50Hz)

    • Max. Cable length to the motor: 600 m (unshielded) 1000m (shielded)

    • According to: EN 60289 / EN 61558

    • Test voltage: L-L 2500 V, AC/50Hz 60s; L-PE 2500 V, AC/50Hz 60s

    • Insulation class: T40/F

    • Protection class: IP00

    • Climatic category: DIN IEC 60068-1

    • Overload: 1,5 x INenn 1 min / h

    • Ambient temperature: 40 °C

    • Design: standing on foot angle



    Typical applications



    • Drive systems for motor drives:


      • Mechanical engineering

      • Elevators / escalators

      • Pipes

      • Conveyor technology

      • Ventilation and air conditioning

      • Robotics

      • Automation technology


    • Power supplies

    • Wind turbines

  • CNW 935

    Three-phase sinusoidal Filter

    CNW 935
    • Nominal Voltage: 400 V
    • Rated current: 4 - 24 A
    • Inductance per strand: 2,4 - 12,5 mH

    Sine wave creation of the output current on the output of a frequency drive.Longer lifetime of motor insulation, noise reduction.



    • Test voltage: L-L 1500 V, DC 1 min; L-PE 2500 V, DC 1 min

    • Überlast: 1,5 x INenn 1 min / h

    • Klimakategorie: DIN IEC 60068-1

    • Rotary field frequency: 0- 60 Hz

    • Short circuit voltage Uk: 8% (with 400V)

    • Voltage drop: 18,4 V/branch (with IN and 50Hz)

    • Max. ambient temperature: 40°C

    • Max. voltage ripple: 5%

    • Clock frequency of converter: ≥ 4kHz

    • Max. cable length to the motor: 600 m (shielded) / 1000 m (unshielded)

    • Protection: IP20



  • CNW 961

    Three-phase sinusoidal filter Plus++

    CNW 961
    • Nominal Voltage: 500 V
    • Rated current: 2 - 60 A
    • Inductance per strand: 0,91 - 33,4 mH

    The REO Sinusfilter Plus++ enables to suppress interference not only on line cables to the motor but also to earth conductors.


    The REO Sinusfilter Plus++ also feeds incurring bearing currents into the DC-link so that these may not cause any damage to the mechanics. REO Sinusfilter Plus++ is used in any kind of application which requires safe mechanical continuous power and reliability.


    Examples of such applications are: Water treatment – especially heat pumps – and materials’ safety in general.



    • Conforming to: EN 61558-2-20

    • Test voltage: L-L 1000 V, DC 1 min; L-PE 2500 V, DC 1 min

    • Rated voltage: U = 3 x 500 V

    • Insulation material class: T40/B

    • Climartic category: DIN IEC 60068-1

    • Overload: 1,5 x INenn 1 min / h



  • CNW M 933

    Three-phase sinusoidal filter

    CNW M 933
    • Rated current: 2 - 37 A
    • Inductance per strand: 1,9 - 29,3 mH

    Sinusoidal input current - save costs and trouble-free operation.


    The mains chokes in fully encapsulated version are specially designed for rough environments and offer a very good mechanical protection of the component. The fully encapsulation allows design up to protection ratings IP 66.


    For particularly long cable lengths of > 100m between inverter and motor the shielded cable for EMI suppression used can cause a capacitive coupling. 


    The sinusoidal filter is a low pass from inductance and capacitance and has a very low resonance frequency. So it is able to generate a largely sinusoidal current. The operation and the loss balance of the asynchronous motor behave like the normal mains operation. The typical motor noise with converter do not occur and a shielded cable to the motor can be dispensed. Losses and heating are greatly minimized and the leakage current will be reduced. Longer motor cable lengths are possible. The motor insulation is protected, thus increasing the service life.


    The sinusoidal filter also attenuates the conducted interference in lower frequency range very good. 



    • Rated voltage: U ≤ 3 x 500 V

    • Max. voltage ripple: 5%

    • Field frequency: 0 - 60 Hz

    • Drive switching frequency: up to 150 A >4kHz, from 150 A >1,5KHz

    • Short-circuit voltage Uk: 8% (bei 400V)

    • Voltage drop: 18,4 V/Strang (bei IN und 50Hz)

    • Max. Cable length to the motor: 600 m (unshielded) 1000m (shielded)

    • According to: EN 60289 / EN 61558

    • Test voltage: L-L 2500 V, AC/50Hz 1 min; L-PE 2500 V, AC/50Hz 1 min

    • Insulation class: T40/F

    • Protection class: IP00

    • Climatic category: DIN IEC 60068-1

    • Overload: 1,5 x INenn 1 min / h

    • Ambient temperature: 40 °C

    • Design: standing on foot angle



    Typical applications



    • Drive systems for motor drives:


      • Mechanical engineering

      • Elevators / escalators

      • Pipes

      • Conveyor technology

      • Ventilation and air conditioning

      • Robotics

      • Automation technology


    • Power supplies

    • Wind turbines

Downloads

  • Download
    Protection Ratings
    pdf

    Protection Ratings

    Discover our brochure about high protection ratings!
    Download
  • Download
    Performance wiith sinusoidal filters
    pdf

    Performance wiith sinusoidal filters

    Save money with unshielded cables
    Download
  • Download
    EMC-Filter Product catalogue
    pdf

    EMC-Filter Product catalogue

    Product catalogue
    Download
  • Download
    High ingress protection ratings make a difference
    pdf

    High ingress protection ratings make a difference

    REO EMC-Filter with IP66
    Download
  • Download
    REO chokes with high protection ratings
    pdf

    REO chokes with high protection ratings

    REO chokes with high protection ratings Fully encapsulated REO chokes
    Download
  • Download
    EMC-Filters overview
    pdf

    EMC-Filters overview

    EMC-Filters The product Prraondguec ta tc aat aglloagnucee
    Download
  • Download
    REO Filter combination CNW 985
    pdf

    REO Filter combination CNW 985

    for a smooth current
    Download
  • Download
    REO Performancehighlights
    pdf

    REO Performancehighlights

    Save costs through longer service life and elimination of shielded cables
    Download
  • Download
    REOWAVE®passive Plus
    pdf

    REOWAVE®passive Plus

    The new generation of harmonic filters
    Download