Power Noise Reduction - save up to 20% energy costs. A mains choker relieved the supply network by compensating the harmonics reactive power. The harmonics and commutation notches are reduced strongly. By using a mains choke the inverter electronics and DC-capacitors will be protected.
Starting currents and current peaks are reduced up to 60%. Mains chokes helps to comply with international power quality standards IEEE 519 or EN 61000-3-2.
Typical applications
Type |
Rated voltage UN [V] |
Rated current IN [A] |
Inductance L [mH] |
Losses P [W] |
Weight [kg] |
CNW 903/3 |
3 x 400 |
3 |
9,800 |
14 |
1,5 |
CNW 903/6 |
6 |
4,880 |
22 |
2,4 |
|
CNW 903/8 |
8 |
3,680 |
25 |
2,8 |
|
CNW 903/10 |
10 |
2,930 |
30 |
3,1 |
|
CNW 903/12 |
12 |
2,450 |
32 |
3,9 |
|
CNW 903/16 |
16 |
1,830 |
42 |
4,4 |
|
CNW 903/25 |
25 |
1,170 |
48 |
6,4 |
|
CNW 903/36 |
36 |
0,810 |
59 |
9,2 |
|
CNW 903/50 |
50 |
0,590 |
76 |
11 |
|
CNW 903/70 |
70 |
0,420 |
96 |
15 |
|
CNW 903/90 |
90 |
0,320 |
130 |
19 |
|
CNW 903/110 |
110 |
0,270 |
150 |
23 |
|
CNW 903/125 |
125 |
0,235 |
180 |
24 |
|
CNW 903/160 |
160 |
0,180 |
210 |
29 |
|
CNW 903/200 |
200 |
0,147 |
290 |
34 |
|
CNW 903/250 |
250 |
0,118 |
350 |
40 |
|
CNW 903/300 |
300 |
0,098 |
360 |
44 |
|
CNW 903/350 |
350 |
0,084 |
430 |
52 |
|
CNW 903/400 |
400 |
0,074 |
590 |
58 |
|
CNW 903/500 |
500 |
0,059 |
660 |
66 |
|
CNW 903/600 |
600 |
0,049 |
790 |
81 |
|
CNW 903/700 |
700 |
0,042 |
820 |
89 |
|
CNW 903/800 |
800 |
0,037 |
1000 |
101 |
|
CNW 903/900 |
900 |
0,033 |
1000 |
130 |
|
CNW 903/1000 |
1000 |
0,029 |
1170 |
130 |
|
CNW 903/1200 |
1200 |
0,024 |
1180 |
147 |
Higher power ratings on request
For Europe |
For USA |
Frequency: 50 Hz |
Frequency: 60 Hz |
Short circuit voltage Uk: 4% (by 400V) |
Short circuit voltage Uk: 9,6% (by 200V) |
Voltage drop: 9,23 V/branch |
Voltage drop: 11,05 V/branch |
Image 1 |
Image 2 |
Image 3 |
||
![]() |
![]() |
![]() |
Type |
Length L [mm] |
Width B [mm] |
Hight H [mm] |
Holder |
A1 |
D / D1 |
D2 |
Conenction |
Image |
|
N1 [mm] |
N2 [mm] |
|||||||||
CNW 903/3 |
95 |
71 |
105 |
30 |
43 |
- |
4.8 x 9 |
- |
1,5 mm² |
1 |
CNW 903/6 |
125 |
76 |
123 |
100 |
45 |
- |
5 x 8 |
- |
2,5 mm² |
1 |
CNW 903/8 |
125 |
85 |
123 |
100 |
55 |
- |
5 x 8 |
- |
2,5 mm² |
1 |
CNW 903/10 |
125 |
85 |
123 |
100 |
55 |
- |
5 x 8 |
- |
2,5 mm² |
1 |
CNW 903/12 |
155 |
95 |
137 |
130 |
56 |
- |
8 x 12 |
- |
5 mm² |
2 |
CNW 903/16 |
155 |
77 |
153 |
130 |
57 |
- |
8 x 12 |
- |
5 mm² |
2 |
CNW 903/25 |
155 |
92 |
185 |
130 |
72 |
- |
8 x 12 |
- |
10 mm² |
2 |
CNW 903/36 |
190 |
92 |
228 |
170 |
68 |
- |
8 x 12 |
- |
16 mm² |
2 |
CNW 903/50 |
190 |
102 |
230 |
170 |
78 |
- |
8 x 12 |
- |
16 mm² |
2 |
CNW 903/70 |
230 |
90 |
270 |
176 |
71 |
- |
9 x 13 |
- |
35 mm² |
2 |
CNW 903/90 |
240 |
107 |
280 |
185 |
85 |
- |
10 x 18 |
- |
50 mm² |
2 |
CNW 903/110 |
240 |
138 |
211 |
185 |
94 |
32 |
10 x 18 |
9 |
25 x 3 |
3 |
CNW 903/125 |
300 |
139 |
263 |
224 |
94 |
32 |
10 x 18 |
9 |
25 x 3 |
3 |
CNW 903/160 |
300 |
157 |
263 |
224 |
107 |
37 |
10 x 18 |
11 |
30 x 3 |
3 |
CNW 903/200 |
300 |
175 |
264 |
224 |
120 |
39 |
10 x 18 |
11 |
30 x 4 |
3 |
CNW 903/250 |
300 |
190 |
264 |
224 |
135 |
39 |
10 x 18 |
11 |
30 x 4 |
3 |
CNW 903/300 |
360 |
176 |
311 |
264 |
127 |
39 |
10 x 18 |
11 |
30 x 4 |
3 |
CNW 903/350 |
360 |
198 |
311 |
264 |
142 |
49 |
10 x 18 |
13 |
40 x 5 |
3 |
CNW 903/400 |
360 |
215 |
311 |
264 |
157 |
49 |
10 x 18 |
13 |
40 x 5 |
3 |
CNW 903/500 |
420 |
206 |
369 |
316 |
144 |
49 |
13 x 20 |
13 |
40 x 5 |
3 |
CNW 903/600 |
420 |
235 |
369 |
316 |
164 |
59 |
13 x 20 |
13 |
40 x 8 |
3 |
CNW 903/700 |
420 |
246 |
368 |
316 |
174 |
58 |
13 x 20 |
13 |
40 x 8 |
3 |
CNW 903/800 |
420 |
255 |
440 |
316 |
174 |
69 |
13 x 20 |
2x 13 |
60 x 5 |
3 |
CNW 903/900 |
480 |
275 |
458 |
356 |
178 |
79 |
13 x 20 |
2x 13 |
60 x 10 |
3 |
CNW 903/1000 |
480 |
275 |
460 |
356 |
178 |
79 |
13 x 20 |
2x 13 |
60 x 10 |
3 |
CNW 903/1200 |
540 |
287 |
483 |
450 |
144 |
79 |
13 x 20 |
2x 13 |
60 x 10 |
3 |